Amphenol Telect, Inc. 20A GMT Fuse Panel w/Dual-Feed 75 Amp input (20HPGMT05FR)
This dual-feed 10/10-position panel operates with multiple 20A GMT fuses that can be mounted adjacent to each other in thermally isolated fuse holders, providing distribution and overload protection for 20 circuits. Each panel can distribute a maximum of 75A per bus (150A total). For fail-safe load sharing to function properly, the returns in the system must be common. The combined total rated load of the panels A and B outputs must not exceed 150A. Designation pin holders are integrated into the panel (one pin holder per fuse). Fail-safe (load sharing) feature provides redundant power to bus A or B if either loses power Panel returns are isolated to allow installation in any system Dual bus (A and B) with 10 fuses per bus Form C relay contacts provide reliable fail alarm connections Fail alarm LEDs provide clear indication of blown fuse and power failures MTBF exceeds 750,000 hours per TR-TSY-000332 Alarm cards and individual fuses can be replaced with the power on Clear polycarbonate cover (94V-0) protects input and output power connectors and wiring Compliant to key industry standards – UL, cUL, NEBS 3, CE